|
PARTIAL DISCHARGES |
|||||||
|
SCOPE
AND OBJECT Resulting from a partial breakdown the voltage difference across the weak part of the dielectric decreases so much that the discharge current is interrupted. Due to the sinusoidal variation of the applied voltage the electrical field strength increases again after the discharge has been extinguished. When the field strength reaches its critical value, a new discharge occurs. Thus discharges take place repeatedly. (Fig. 14.1). |
|||||||
|
|||||||
|
The situation is enlightened by the simple analogue circuit of a cavity (Fig. 14.2). Ca is the capacitance of the whole insulating gap, the spark-gap and the capacitance Cc represent the cavity and the capacitance Cb represents the dielectric in series with Cc. When the voltage Uc across Cc has incrased enough, the spark-gap ignites. The capacitance Cc discharges and the voltage difference across the cavity vanishes within 1...1000 ns. The discharge magnitude or apparent charge q and the voltage Uc are related by the following equation: |
|||||||
|
|||||||
| The discharge gives rise to a current pulse, which caused a fast voltage change at the terminals of the transformers; this charge can be measured by means of a capacitive voltage divider and a pulse transformer. | |||||||
|
|||||||
|
The partial discharges do not lead to an immediate breakdown. They have, however, other effects on the insulating medium:
|
|||||||
|
These phenomena result in degradation of the dielectric properties of the insulating medium, and increase of losses. The object of the partial discharge measurement is to reveal the above mentioned weak parts of the dielectric, which may cause destruction of the transformer in service. |
|||||||
| CIRCUIT MEASUREMENT | |||||||
|
|||||||
| PERFORMANCE
OF THE MEASUREMENT The measurement is based on observing and evaluating the apparent charge in accordance with the standard IEC 270. The measuring system is basically a wide-band system as shown on Fig. 14.3 |
|||||||
| PARTIAL
DISCHARGE MEASUREMENT The voltage is increased stepwise, first up to measuring voltage U2, when the occurence of discharge is checked. The test voltage is increased to the pre-stress voltage level U1 and help there for a duration according to standard. The pre-stress voltage is applied in order to ignite the discharges. Thereafter, the voltage is rapidly reduced to U2 and maintained at this value for the agreed duration of time tmes (Fig. 14.4). During this period the occurence of discharges is being checked at the terminals of the transformer. The voltage measurement is carried out at the high voltage side of the transformer to be tested (Fig. 14.3). |
|||||||
|
|||||||
| According to the standard IEC 270 the test is carried out using the following values of test voltages between line and neutral terminal and test period durations: | |||||||
|
|||||||
| RESULTS The partial discharge measurement test report shows the test performance and the measuring values.. |
|||||||