INSTALLATION |
||||||||||||||||||||||||||||||||||||
|
A cooling
air supply must be provided for transformers placed indoor or in a metal
enclosure. |
||||||||||||||||||||||||||||||||||||
|
FORMULA:
P = Transformer total losses (in kW) S = Entry surface (without possible grate) in sq. mt. S1 = Exit surface (without possible grate) in sq. mt. H = Distance between the two surface in mt. |
||||||||||||||||||||||||||||||||||||
![]() |
||||||||||||||||||||||||||||||||||||
| If
a sufficient cooling surface cannot be provided, it is necessary to employ
a mechanical activated means of ventilation. The air flow should be 4.5 mc per minute for each kW loss which corresponds to an air temperature rise of 12° C approxymately. |
||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||
|
INSULATION DISTANCE For a proper transformer installation it is necessary to respect the values stated in the following table. |
||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||