|
MEASUREMENT OF ZERO-SEQUENCE IMPEDANCE |
|||||
|
PURPOSE
OF THE MEASUREMENT
|
|||||
|
The zero-sequence impedance is usually measured for star or zig-zag connected windings of the transformer. The measurement is carried out by supplying a current of rated frequency between the parallel connected phase terminal. The zero-sequence impedance per phase is three times the impedance measured in this way. The zero-sequence impedance is needed for earth-fault protection and earth-fault current calculations. |
|||||
|
MEASURING CIRCUIT AND PERFORMANCE OF MEASUREMENT |
|||||
|
|||||
|
The zero-sequence impedance is dependent on the current flowing through the winding. It is measured as a function of test current, and when necessary the final result is obtained by extrapolation. |
|||||
|
RESULT
|
|||||
|
The zero-sequence impedance is usually given as a percentage of the rated phase impedance. In the test report the zero-sequence impedance value at the principal tapping is stated. |
|||||