MEASUREMENT OF ZERO-SEQUENCE IMPEDANCE

   
 
PURPOSE OF THE MEASUREMENT
 

The zero-sequence impedance is usually measured for star or zig-zag connected windings of the transformer. The measurement is carried out by supplying a current of rated frequency between the parallel connected phase terminal. The zero-sequence impedance per phase is three times the impedance measured in this way. The zero-sequence impedance is needed for earth-fault protection and earth-fault current calculations.

   
 

MEASURING CIRCUIT AND PERFORMANCE OF MEASUREMENT

 

Fig. 9.1

Circuit for zero-sequence impedance measurement
G1 supply regulator, T1 transformer to be tested, T2 current transformer, P2 voltmeter, P3 ammeter, I test current.
 

The zero-sequence impedance is dependent on the current flowing through the winding. It is measured as a function of test current, and when necessary the final result is obtained by extrapolation.

   
 
RESULT
 

The zero-sequence impedance is usually given as a percentage of the rated phase impedance.

In the test report the zero-sequence impedance value at the principal tapping is stated.